Heat Pump for Small Capacity Type J-IIIL Series AJY090LELAH

Outdoor unit

Outdoor Unit :
AJY090LELAH
Download :
Catalogue

Features

  • Compact design
  • Advanced technologies for high efficiency
  • Long piping length
  • Top class indoor unit connection
  • High static pressure
  • Best-in-class low-noise operation

Capacity

Cooling  28.0 kW
Heating  28.0 kW

Specification

Rated Capacity Range 10
Maximum Connectable Indoor Unit 1 - 25
Scroll
Power source Phase 3 phase
Voltage ~400 V
Frequency 50 Hz
Capacity Cooling 28.0 kW
Heating 28.0 kW
Input Power Cooling 8.59 kW
Heating 6.61 kW
EER Cooling 3.26 W/W
COP Heating 4.24 W/W
Air Flow Rate 9,000 m³/h
Sound Pressure Level Cooling 54 dB(A)
Heating 57 dB(A)
Net Dimensions Height 1,428 mm
Width 1,080 mm
Depth 480 mm
Net Weight 177 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 7.5 (15.7) kg
Connection Pipe Diameter Liquid 9.52 mm
Gas 22.20 mm
Total pipe length 400 m
Max. height difference 50 m
40 m
Operation Range Cooling -15 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.

Dimensions

Outdoor Unit : AJY090LELAH

Outdoor unit